A 6-bit “variac casero”

Kragen Javier Sitaker, 02020-06-06 (22 minutes)

Watching the YouTube channel of Espacio de César, I was amused to see him describe a “homemade 8-bit variac” (“variac casero de 8 bits”). He suggests winding 8 secondaries of different sizes on a single transformer whose primary is connected to 240 VAC: one that produces 1 VAC, one that produces 2 VAC, and so on up to 128 VAC. (He’s using a microwave-oven transformer, but recommends using a smaller one instead.) By connecting these to 8 pairs of banana-plug terminals in a metal box, you get a sort of variac; for example, if you want 42 volts, you can put in series the 2-VAC, the 8-VAC, and the 32-VAC winding with two jumper wires.

But there are other ways you can get 42 volts; for example, you can use the 32-VAC winding in series with the 16-VAC winding, then wire up the 4-VAC and 2-VAC windings backwards in series with that.

Balanced ternary gets you to 364 VAC in 1-volt increments in only 6 secondary windings

This suggests instead using balanced ternary. With a 1 VAC winding and a 3 VAC winding, you can get 1 VAC, 2 VAC (by wiring the two windings in series in opposition), 3 VAC, or 4 VAC (by wiring them in series). By adding 9 VAC, 27 VAC, 81 VAC, and 243 VAC windings, you can reach any voltage up to 364 VAC in 1-VAC steps, and this is the minimal number of windings you need to reach it.

Multitap secondary windings can deliver even more voltages with less terminals

That requires 12 banana-plug terminals, though. If you want to minimize the number of terminals rather than the number of windings, you might be able to do better with center-tapped windings.

For example, if you have one winding with three terminals whose two segments are 1 V and 2 V, you get 1, 2, and 3 VAC with three terminals; a second winding with three terminals whose two segments are 7 and 14 volts gives you all voltages from 1 to 24 volts AC; a third winding of 49 and 98 volts gives you all voltages from 1 to 171 VAC. That’s 9 terminals; a fourth center-tapped winding, with 343 and 686 volts in its segments, bringing us to 12 terminals as before, might then bring us from 1 to 1200 volts AC in one-volt steps. Or we could use a fourth 343-volt winding with no center-tap and get up to 514 volts with only 11 terminals rather than the 12 required by the balanced-ternary scheme to reach 364.

But what if we have four terminals on a winding? You could have, for example, a winding with a 1-VAC segment, a 3-VAC segment, and a 2-VAC segment, in that order; this gives you 1, 2, 3, 4, 5, and 6 volts between its six different pairs of terminals. A second four-terminal winding with 13, 39, and 26 volts on its segments gets us 1-84 volts. A third winding with 169, 507, and 338 volts on its segments gets us 1-1098 volts, with the same 12 terminals that would give us 1-64 volts with César’s binary scheme, 1-364 volts with the balanced-ternary scheme, or 1-1200 volts with the single-center-tapped scheme.

So it seems like the single-center-tapped scheme is optimal, at least to minimize the number of voltages you can get for a given number of terminals. The double-center-tapped scheme is very nearly as good, though, and it uses less jumper wires: you can reach any voltage up to 1098 volts with only two jumpers instead of the three you might need with the single center-tap.

One-volt precision is maybe more important when you’re at 2 or 3 volts than when you’re at 950 volts, so it would be nice if we could separate the voltage levels a bit more at higher voltages; unfortunately, the voltages on the various secondary windings do sum linearly, so you can’t avoid this completely. But if you have one winding with segments of 1, 3, and 2 V and a second one with segments of 15 and 30 V, then you can do any one-volt voltage from 1-6 volts, 9-21 volts, 24-36 volts, and 39-51 volts, with just seven terminals and a single jumper.

subs = lambda items: set(sum(items[i:j])
                         for j in range(len(items)+1)
                         for i in range(j))
combos = lambda subses: {0} if not subses else set(a+b
    for c in subses[0] for a in [c, 0, -c] for b in combos(subses[1:]))
combos([subs([1]), subs([3]), subs([9]), subs([27]), subs([81]), subs([243])]
    ) == set(range(-364, 365))
combos([subs([1, 2]), subs([7, 14]), subs([49, 98]), subs([343, 686])]
    ) == set(range(-1200, 1201))
combos([subs([1, 3, 2]), subs([13, 39, 26]), subs([169, 507, 338])]
    ) == set(range(-1098, 1099))

I don’t think we can do better by connecting triples of windings together in a Y configuration, like some BLDC motors, because the 1-3-2 setup already gives us six distinct voltages for the six distinct pairs of terminals, and they cover a contiguous range of integers.

A practical configuration

I think that, if you were going to do this in real life, the most practical configuration would use a single high-voltage winding with two terminals and two low-voltage windings with four terminals each, with a first winding of segments of ½, 1½, and 1 volt and a second winding of segments of 8, 24, and 16 volts. This gives you 0.5-volt resolution for 0-3 volts, 5-11 volts, and 13-19 volts, and 2-volt-or-better resolution up to 51 volts, all configured with a single jumper. This is not enough to kill you unless you are astonishingly fortunate.

The high-voltage winding might be 120 volts, which in combination with the low-voltage windings gives you voltages up to 171 volts, with an 18-volt gap between 51 and 69 volts; all of this for ten terminals and three secondary windings (plus the primary).

Ganging up two transformers

Now, if transistor cores are abundant and you just want to keep windings to a minimum, you could get a more favorable spread of high and low voltages by putting two separate transformers in the box, one fed from the power line with two to four terminals on its secondary brought out to the front panel, and a second transformer connected only to front-panel terminals, perhaps with two windings with three or four terminals each, either of which can be connected as a “primary” to the secondary of the first transformer. One reasonable winding configuration for the second transformer might be turns numbers of 1n-3n-2n on one winding and 10n-18n on the other. This affords 18 different stepups as low as 3:5 and as high as 1:28, including 2, 2½, 3, 5, 6, 7, 9, 10, 14, 18, and 28; and of course their reciprocals as stepdowns.

import fractions
' '.join(str(x) for x in sorted(f for n in subs([1, 3, 2])
                                  for d in subs([10, 18])
                                  for f in [fractions.Fraction(n, d),
                                            fractions.Fraction(d, n)]))

So if you had a center-tapped winding on the primary transformer with a 14-volt segment and a 134-volt segment, you could get 111 different voltages out of the combination of the two transformers, ranging from ½ VAC up to 4144 VAC. The full list is:

1/2 7/9 1 7/5 3/2 14/9 2 7/3 5/2 14/5 3 28/9 35/9 21/5 14/3 67/14
37/7 28/5 7 67/9 74/9 42/5 67/7 74/7 67/5 14 201/14 74/5 134/9 111/7
148/9 134/7 148/7 67/3 70/3 335/14 74/3 185/7 134/5 28 201/7 148/5
268/9 222/7 296/9 35 335/9 201/5 370/9 42 222/5 134/3 140/3 148/3
252/5 268/5 296/5 63 196/3 67 70 74 392/5 402/5 84 444/5 98 126 392/3
134 140 148 196 670/3 740/3 252 268 296 335 370 392 402 444 1340/3
2412/5 1480/3 2664/5 603 1876/3 666 670 2072/3 740 3752/5 804 4144/5
888 938 1036 1206 3752/3 1332 1340 4144/3 1480 1876 2072 2412 2664
3752 4144

' '.join(str(x) for x in sorted(set(f*v for n in subs([1, 3, 2])
                                        for d in subs([10, 18])
                                        for v in subs([14, 134])
                                        for f in [fractions.Fraction(n, d),
                                                  fractions.Fraction(d, n),
                                                  1])))

Or, as decimal approximations:

0.50 0.78 1.00 1.40 1.50 1.56 2.00 2.33 2.50 2.80 3.00 3.11 3.89
4.20 4.67 4.79 5.29 5.60 7.00 7.44 8.22 8.40 9.57 10.57 13.40
14.00 14.36 14.80 14.89 15.86 16.44 19.14 21.14 22.33 23.33 23.93
24.67 26.43 26.80 28.00 28.71 29.60 29.78 31.71 32.89 35.00 37.22
40.20 41.11 42.00 44.40 44.67 46.67 49.33 50.40 53.60 59.20 63.00
65.33 67.00 70.00 74.00 78.40 80.40 84.00 88.80 98.00 126.00
130.67 134.00 140.00 148.00 196.00 223.33 246.67 252.00 268.00
296.00 335.00 370.00 392.00 402.00 444.00 446.67 482.40 493.33
532.80 603.00 625.33 666.00 670.00 690.67 740.00 750.40 804.00
828.80 888.00 938.00 1036.00 1206.00 1250.67 1332.00 1340.00
1381.33 1480.00 1876.00 2072.00 2412.00 2664.00 3752.00 4144.00

' '.join('%.2f' % float(x)
         for x in sorted(set(f*v for n in subs([1, 3, 2])
                                 for d in subs([10, 18])
                                 for v in subs([14, 134])
                                 for f in [fractions.Fraction(n, d),
                                           fractions.Fraction(d, n),
                                           1])))

Note that this still requires only 10 terminals: three on the main transformer’s secondary winding, four on the auxiliary transformer’s low-turns winding, and three on the auxiliary transformer’s high-turns winding. Like the single-transformer “practical” configuration described above, it also requires four windings and at most two jumpers; it can produce fewer distinct voltages (only 111 instead of 153) but they are spaced out in a much more useful fashion: no more than 0.5 volts apart up to 3.1 volts, no more than 1 V apart up to 5.6 volts, no more than 2 V apart up to 10.6 volts, no more than 4 volts apart up to 46 volts, and so on.

It should be straightforward to come up with a better set of numbers for the windings, too, that give even more evenly spaced voltages, and perhaps at rounder numbers, although that aim seems to be in conflict with the aim of increasing the number of distinct voltages.

The above ignores the possibility of using the windings on the second transformer in autotransformer mode, so a larger number of configurations is actually possible; for example, you could hook up 14 volts to the 10n-turn winding segment and get 25.2 volts off the 18n-turn winding segment, a number which isn’t in the above list. This relies on the primary transformer to provide galvanic isolation, which ought to be fine.

It’s somewhat dubious whether you’d really want to use the higher voltages on such a gadget; they might need to be insulated to a degree that would make them impractical for the high currents encountered at low voltages.

Lightswitch reconfiguration

A lower-hassle way to get such flexibility, with only a single transformer, would be to mechanically switch the mains power between different primary windings. Two everyday single-pole double-throw lightswitches of the type commonly used to wire up hallway lights --- so that you can turn them on or off from either end of the hallway --- suffice to select among four of the six possibilities offered by a primary winding with two center taps, without any possibility of a short circuit. If the segments have a winding configuration 1n-1n-2n, then the four possibilities are 1n, 2n, 3n, and 4n; if instead they are 7n-1n-56n, then the four possibilities are 1n, 8n, 57n, and 64n.

This possibility of 1n, 8n, 57n, and 64n turns on the primary could be seen as a selectable multiplier of the secondary voltage: respectively 64, 8, 64/57 (about 1.12), and 1. Suppose that when the primary side is set to 8x, the medium voltage, the secondary side is like the low-voltage setup described above under “A practical configuration”: a first winding of segments of ½, 1½, and 1 volts and a second winding of segments of 8, 24, and 16 volts. This gives you ½-volt resolution for 0-3 volts, 5-11 volts, and 13-19 volts, and 2-volt-or-better resolution up to 51 volts, all configured with a single jumper. Setting the primary side to 64/57 gets you roughly the same set of low voltages boosted by about 10%. But setting the primary side to 1x, the same secondary-side configurations give you 62.5-millivolt resolution from 0-375 mV, 625 mV-1.375 V, and 1.625-2.375 V, and ¼-volt-or-better resolution up to 6.375 volts.

Or, if you set the primary side to 64x — connecting only the middle segment of the primary winding — you get 4-volt resolution for 0-24 volts, 40-88 volts, and 104-152 volts, and 16-volt-or-better resolution up to 408 VAC. Ideally this 64x setting would be protected somehow so you didn’t do it by accident. There’s probably a reason they don’t make power variacs with two sliders...

Since 63 millivolts to 408 volts is an unreasonably large range for a single apparatus — 100 watts at 408 volts is only 250 mA, while at 63 millivolts it would be sixteen hundred amps — maybe a better choice is to use a single four-terminal winding on the secondary side. It could be wired, say, 2-5-4, which can produce multipliers [2, 4, 5, 7, 9, 11], and windings on the primary side could be configured, say, 5n-2n-11n, providing divisors of 2n, 7n, 13n, and 18n, since 11n and 5n are inaccessible with the two-lightswitch configuration. This design is amusingly analogous to a trucker’s 4×6 gearshift, except that truckers’ gear ratios are a lot closer together.

If we set the lowest available voltage here to 1 VAC (2 on the secondary, 18n on the primary), then our 23 available voltages are 1.0, 1.38, 2.0, 2.5, 2.57, 2.77, 3.46, 3.5, 4.5, 4.85, 5.14, 5.5, 6.23, 6.43, 7.62, 9.0 (two ways), 11.57, 14.14, 18.0, 22.5, 31.5, 40.5, 49.5.

sorted([round(9*v/d, 2) for v in subs([2, 5, 4]) for d in [2, 7, 13, 18]])

This is an entirely reasonable set of voltages for a ghettobotics lab benchtop power supply, except that they’re AC voltages. If you rectify these voltages and charge capacitors with them, they get higher by a factor of 2½: 1.41, 1.96, 2.83, 3.54, 3.64, 3.92, 4.9, 4.95, 6.36, 6.85, 7.27, 7.78, 8.81, 9.09, 10.77, 12.73, 12.73, 16.36, 20.0, 25.46, 31.82, 44.55, 57.28, 70.0.

This approach is also a lot more windings-efficient than the approach of varying only the secondary windings: it never uses less than 11% of the primary windings nor less than 18% of the secondary windings, so the transformer never needs to be more than about six times bigger than the minimal 50Hz transformer for whatever you’re doing at the moment. By contrast, with windings of 1V, 3V, 9V, and 27V, the balanced ternary approach is using 2.5% of its secondary windings when it’s outputting 1V. Normally the primary and secondary windings need to be about the same size because their cross-sectional areas per turn vary in nearly exact proportion to their numbers of turns, so at 1 V it can only carry 1/40 of its maximum power.

What’s the actual turns ratio n? If our input is 240VAC, it’s about 26.67: say, 133 turns, 53 turns, and 293 turns in the three segments of the primary, if the secondary is actually wired with 2 turns, 5 turns, and 4 turns. If you’re winding the transformers by hand, using an additional stepdown transformer (or two!) would be a great idea, just so you don’t have to thread a wire through your transformer core over 900 times. This, though, suggests a return to the approach of the previous section, wherein each winding gives you an opportunity to reconfigure.

An 8-lightswitch reconfigurable design with two transformers but only two jacks

So, suppose we have a primary transformer with two center-taps on its primary hooked to the wall current through two SPDT switches, and the two center-taps on its secondary allow you to use two more SPDT switches to select one of four possible parts of the secondary, and those are connected to the primary of a second transformer via two more SPDT switches to select one of four possible parts of its primary, and on its output we have two more SPDT switches which hook up the output socket to it. No jumper wires and no possibility of shorting a winding with them. What does that look like? What kind of turns ratios can it give us?

I’m tired of designing, so I generated the random configuration ([25, 9, 32], [5, 2, 11], [25, 24, 28], [7, 2, 12]). That is, the first transformer has a primary winding with a 25-turn segment, an 9-turn segment, and a 32-turn segment, and a secondary winding with a 5-turn segment, a 2-turn segment, and an 11-turn segment; the second transformer has a 25-24-28 primary and a 7-2-12 secondary. (Maybe all the turns numbers are multiplied by some constant such as 1.5 or 2, since 2 turns might not be enough to couple well to the magnetic core.) What possibilities does this offer?

import random

def config(m):
    x = range(2, m)
    random.shuffle(x)
    x = sorted(x[:3])
    x[0], x[1] = x[1], x[0]
    return x

config(20), config(10), config(20), config(10)

I’m tired of calculating too, so I wrote code to calculate.

spdt = lambda (a, b, c): sorted([b, a+b, b+c, a+b+c])

ratios = lambda p, s: sorted(set(fractions.Fraction(n, d)
                                 for d in p for n in s))
' '.join(str(f) for f in ratios(spdt([25, 9, 32]), spdt([5, 2, 11])))
' '.join(str(f) for f in ratios(spdt([25, 24, 28]), spdt([7, 2, 12])))

This gives us the possible voltage ratios for the first transformer 1/33 2/41 1/17 7/66 7/41 13/66 7/34 2/9 3/11 13/41 13/34 18/41 9/17 7/9 13/9 2 and for the second transformer 2/77 1/26 2/49 1/12 9/77 9/52 2/11 9/49 7/26 3/11 2/7 3/8 21/52 3/7 7/12 7/8. These do indeed result in 256 different voltages, which range from about 0.2 volts up to 420 volts:

rs = sorted(set(240*t1*t2 for t1 in ratios(spdt([25, 9, 32]), 
                                           spdt([5, 2, 11]))
                          for t2 in ratios(spdt([25, 24, 28]),
                                           spdt([7, 2, 12]))))
min(rs), max(rs), len(rs)

Specifically, the output voltages are 0.189 0.280 0.297 0.304 0.367 0.450 0.478 0.543 0.576 0.606 0.661 0.850 0.976 0.979 1.039 1.064 1.176 1.228 1.259 1.283 1.322 1.336 1.368 1.385 1.576 1.650 1.672 1.700 1.818 1.900 1.929 1.958 1.977 1.983 2.017 2.026 2.051 2.078 2.121 2.129 2.150 2.177 2.383 2.443 2.517 2.567 2.593 2.672 2.727 2.737 2.927 2.937 2.975 3.106 3.117 3.152 3.193 3.300 3.345 3.415 3.529 3.745 3.801 3.850 3.939 4.034 4.053 4.118 4.242 4.301 4.390 4.406 4.444 4.628 4.675 4.728 4.789 4.848 4.887 5.017 5.186 5.294 5.455 5.525 5.701 5.775 6.050 6.234 6.341 6.364 6.829 6.853 6.942 7.092 7.179 7.273 7.450 7.526 7.619 7.647 7.651 8.182 8.235 8.552 8.595 8.683 8.780 8.895 8.984 9.004 9.076 9.231 9.545 9.697 9.796 10.244 10.280 10.588 10.726 10.909 11.032 11.175 11.329 11.707 11.901 12.022 12.315 12.353 12.468 12.727 12.893 13.171 13.303 13.333 13.476 13.506 13.836 13.977 14.118 14.150 14.359 14.545 14.848 14.851 15.238 15.366 15.556 15.882 16.548 16.684 16.855 17.561 17.622 17.727 17.851 18.236 18.462 18.529 18.701 19.091 19.157 19.353 19.592 19.955 20.000 20.260 20.488 20.754 21.176 21.538 21.742 21.818 21.991 22.273 22.857 23.102 23.337 23.902 24.545 24.706 25.027 26.218 26.434 27.576 28.052 28.368 28.537 28.736 28.824 28.889 30.105 30.732 31.111 32.308 32.613 33.939 34.208 34.286 34.412 34.652 35.854 36.303 37.059 38.182 39.328 39.512 40.000 40.519 41.364 42.552 43.235 44.390 45.157 46.667 47.647 50.256 50.909 51.312 53.333 53.529 54.454 56.104 57.273 60.000 61.463 63.030 63.673 66.585 70.000 74.118 75.385 80.000 80.294 83.077 87.273 88.163 92.195 93.333 94.545 99.048 108.889 111.176 129.231 130.000 130.909 137.143 140.000 148.571 163.333 180.000 193.846 202.222 205.714 280.000 303.333 420.000.

' '.join('%.3f' % float(f) for f in rs)

This randomly generated configuration is maybe not a super great design but it’s in some sense reasonable. Half the values are below 12 volts, there are 256 distinct values, the values are mostly only a couple percent apart in the middle of the range, and the range covers over three orders of magnitude. Over most of the range the design has considerably more precision in the turns ratio than the margin of error on the mains voltage.

This is kind of overkill, although the transformers are much more manageable. Maybe a single SPDT per winding with a single center tap on each winding and two center taps on the final output would be adequate: three lightswitches to “select a range” and then four output terminals to give you six voltages simultaneously, 48 settings in all.

Topics